Chapter 9

Additional Requirements for Each Purpose Group

Chapter 9 sets out purpose-group-specific fire safety requirements that supplement the general provisions in Chapters 1–8. Each clause addresses the unique risks, occupancy patterns, and structural characteristics of one of the nine Purpose Groups (I–VIII plus Others). Requirements range from simplified exit provisions for small houses (PG I) to detailed compartmentation, smoke-control, and sprinkler thresholds for hospitals, factories, warehouses, and assembly buildings. Clause 9.9 covers special building types including conservation shophouses, buildings under construction, engineered timber structures, mega underground developments, and flammable refrigerant restrictions.

Scope: All buildings in Singapore classified under Purpose Groups I through VIII and special building types covered by Clause 9.9. Requirements supplement and, where they conflict with, take precedence over Chapters 1–8.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Warehouse compartment size triggers full compliance with Cl.9.8.3 for aboveground warehouses >700 m² and basements >100 m²; compliance includes sprinkler, smoke control, and storage height controls.

    CriticalCl.9.8.1b.(2)
  • Chemical/HazMat warehouse: compartment walls must be ≥2-hr FRR regardless of fire protection system; Class 3 HazMat requires masonry construction; no basement storage of hazardous materials.

    CriticalCl.9.8.4c, Table 9.8G
  • Single-storey warehouse max compartment: 12,000 m² (sprinkler, all hazards); 3,000 m² (non-sprinkler, normal hazard); 2,000 m² (non-sprinkler, high hazard). Max storage height: 18 m (sprinkler single-storey).

    CriticalTable 9.8A
  • Engineered smoke control system is required for aboveground warehouse compartments >5,000 m² or underground warehouse compartments >2,000 m².

    CriticalCl.9.8.3e.(4)
  • Cold rooms: non-sprinkler-protected buildings with aggregate cold room area >10 m² require 1-hr outer compartment; max aggregate ≤100 m² per compartment. Sprinkler-protected threshold is >20 m² trigger, max 700 m² aggregate per compartment.

    CriticalCl.9.8.2a
  • Category 2 and 3 FAMCPs are subject to Fire Certificate scheme. A-FAMCPs and U-FAMCPs must be protected by sprinklers or clean agent fire extinguishing systems.

    CriticalCl.9.8.5f, Cl.9.8.5g
  • Storage height signs must be posted at intervals ≤15 m on warehouse walls; red line drawn at no-storage line with lettering ≥100 mm.

    ImportantCl.9.8.3d

Compliance thresholds

ParameterValueConditionClause
Single-storey warehouse max compartment (sprinkler-protected, all hazards)12,000 m²Sprinkler-protected single-storey warehouseTable 9.8A
Single-storey warehouse max compartment (non-sprinkler, normal hazard)3,000 m²Non-sprinkler-protected, normal storage hazardTable 9.8A
Single-storey warehouse max compartment (non-sprinkler, high hazard)2,000 m²Non-sprinkler-protected, high storage hazardTable 9.8A
Basement warehouse max compartment (sprinkler only, non-sprinkler not permitted)3,000 m²Sprinkler-protected basement warehouseTable 9.8A
Max storage height — single-storey sprinkler-protected warehouse18 mSingle-storey sprinkler-protected warehouseTable 9.8A
Max storage height — non-sprinkler-protected warehouse (transient/staging)2.5 mNon-sprinkler-protected warehouse loading/unloading areaCl.9.8.3d.(5)
Engineered smoke control threshold — aboveground warehouse>5,000 m²Aboveground sprinkler-protected warehouse compartmentCl.9.8.3e.(4)(a)
Engineered smoke control threshold — underground warehouse>2,000 m²Underground (basement) warehouse compartmentCl.9.8.3e.(4)(a)
Cold room aggregate area — non-sprinkler outer compartment trigger>10 m²Non-sprinkler-protected buildings with combustible cold room panelsCl.9.8.2a.(1)
Cold room max aggregate area per compartment (non-sprinkler)100 m²Non-sprinkler-protected, combustible cold room panelsCl.9.8.2a.(1)
Cold room max aggregate area per compartment (sprinkler)700 m²Sprinkler-protected, combustible cold room panelsCl.9.8.2a.(2)
SA-FAMCP (Cat 1) max floor area200 m² (total car parking decks)Category 1a/1b small aboveground FAMCPCl.9.8.5c.(1)–(2)
SA-FAMCP (Cat 1) max cubical extent1,400 m³Category 1 FAMCPCl.9.8.5c.(1)
U-FAMCP (Cat 3) max parking depth28 mUnderground FAMCPTable 9.8.5g.(1)
U-FAMCP (Cat 3) max floor area2,000 m² (total car parking decks)Underground FAMCP per compartmentTable 9.8.5g.(1)
Max AFA for single-staircase warehouse floor200 m²Single exit staircase, aboveground warehouse floorCl.9.8.1a.(1)(c)

Interactive decision tree

Start

What type of PG VIII storage/general use is being assessed?