Chapter 9

Additional Requirements for Each Purpose Group

Chapter 9 sets out purpose-group-specific fire safety requirements that supplement the general provisions in Chapters 1–8. Each clause addresses the unique risks, occupancy patterns, and structural characteristics of one of the nine Purpose Groups (I–VIII plus Others). Requirements range from simplified exit provisions for small houses (PG I) to detailed compartmentation, smoke-control, and sprinkler thresholds for hospitals, factories, warehouses, and assembly buildings. Clause 9.9 covers special building types including conservation shophouses, buildings under construction, engineered timber structures, mega underground developments, and flammable refrigerant restrictions.

Scope: All buildings in Singapore classified under Purpose Groups I through VIII and special building types covered by Clause 9.9. Requirements supplement and, where they conflict with, take precedence over Chapters 1–8.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Each guestroom/accommodation unit accessed via internal corridor must be compartmented by ≥1-hr FRR construction; corridor doors ≥½-hr FRR with self-closing device.

    CriticalCl.9.7.2a.(1)–(2)
  • Non-naturally-ventilated internal corridors in hotel/hostel buildings must be subdivided by smoke barriers: ≤45 m (sprinkler-protected) or ≤30 m (non-sprinkler).

    CriticalCl.9.7.2d.(1)
  • Theatre/cinema/concert hall seating >500 persons with fly tower: stage must be separated from auditorium by ≥1-hr proscenium wall; proscenium opening protected by ≥1-hr fire curtain (or smoke curtain with sprinklers and smoke control on stage).

    CriticalCl.9.7.3b.(4)
  • Multi-tier/level seating auditorium requires both automatic sprinkler system and engineered smoke control system.

    CriticalCl.9.7.3b.(5)(a)
  • Capsule hotels: entire building must be sprinkler-protected; at least one sprinkler inside each capsule at ≥50 kPa and ≥56 L/min; smoke/heat detector in each capsule; occupancy/motion sensor in each capsule linked to main alarm panel.

    CriticalCl.9.7.2f.(4)
  • At least 10% of guestrooms/accommodation units must have visual alarm systems (staff quarters exempted).

    ImportantCl.9.7.2e
  • ORA total occupant load per F&B outlet must not exceed 200 persons; if exceeded, alternate rear exit to back lane or safe external space is required.

    ImportantCl.9.7.4a.(2)

Compliance thresholds

ParameterValueConditionClause
Smoke barrier interval — non-naturally-ventilated corridor (sprinkler)45 mSprinkler-protected hotel/hostel buildingCl.9.7.2d.(1)(a)
Smoke barrier interval — non-naturally-ventilated corridor (non-sprinkler)30 mNon-sprinkler hotel/hostel buildingCl.9.7.2d.(1)(b)
Natural ventilation openings for internal corridor (hotel)≥15% of floor area, ≤9 m from any part of corridorNaturally ventilated internal corridor in hotel/hostelCl.9.7.2a.(3)
Seats per row trigger — proscenium wall requirement>500 persons, with fly towerTheatres/concert hallsCl.9.7.3b.(4)(a)
Min proscenium wall FRR1 hourTheatres/concert halls >500 persons with fly towerCl.9.7.3b.(4)(a)
Smoke vent area — single-tier auditorium≥2.5% of floor areaSingle-tier auditorium smoke vents in lieu of engineered smoke controlCl.9.7.3b.(5)(a)(i)
Max distance from smoke vent in auditorium12 mNo part of auditorium to be more than this distance from a ventilation openingCl.9.7.3b.(5)(a)(iii)
Min smoke vent size600 mm × 600 mmAuditorium smoke ventsCl.9.7.3b.(5)(a)(ii)
Max F&B outlet ORA occupant load (no alternate exit)200 personsF&B outlet ORA total occupant loadCl.9.7.4a.(2)
Min clear five-foot way width (ORA along covered walkway)1.2 mORA along covered walkway of F&B outletCl.9.7.4b.(1)(a)
Capsule hotel room max AFA60 m²Per capsule hotel guestroomCl.9.7.2f.(2)(b)
Capsule hotel room max occupant load20 personsPer capsule hotel guestroomCl.9.7.2f.(2)(c)
Min capsule sprinkler operating pressure50 kPaIn-capsule sprinkler headCl.9.7.2f.(4)(a)
Min capsule sprinkler flow rate56 L/minIn-capsule sprinkler headCl.9.7.2f.(4)(a)

Interactive decision tree

Start

What is the primary PG VII use?