Digital Compliance Tool

SCDF Fire Code 2023 Decision Workflows

Search by clause, browse all 11 chapters, and use structured decision trees to understand the compliance path before confirming with the official SCDF code and your Qualified Person.

Beta Navigation Aid

This viewer is an interpretive workflow tool. It supports fire safety planning, but it does not replace the official Fire Code, SCDF circulars, or professional judgement.

Read the launch note

Chapter 9

Additional Requirements for Each Purpose Group

Chapter 9 sets out purpose-group-specific fire safety requirements that supplement the general provisions in Chapters 1–8. Each clause addresses the unique risks, occupancy patterns, and structural characteristics of one of the nine Purpose Groups (I–VIII plus Others). Requirements range from simplified exit provisions for small houses (PG I) to detailed compartmentation, smoke-control, and sprinkler thresholds for hospitals, factories, warehouses, and assembly buildings. Clause 9.9 covers special building types including conservation shophouses, buildings under construction, engineered timber structures, mega underground developments, and flammable refrigerant restrictions.

Scope: All buildings in Singapore classified under Purpose Groups I through VIII and special building types covered by Clause 9.9. Requirements supplement and, where they conflict with, take precedence over Chapters 1–8.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Sprinklers are mandatory for healthcare occupancy with patient accommodation where: more than one storey, located on upper storey, or largest non-compartmented AFA exceeds 750 m².

    CriticalCl.9.3.2a
  • Patient accommodation areas containing beds shall NOT be located in basement storeys.

    CriticalCl.9.3.2b.(1)
  • Every upper storey with patient accommodation must have at least one area of refuge sized at 2.8 m²/person (or by bed dimension 2.55 m × 1.1 m for hospital/nursing home).

    CriticalCl.9.3.2b.(4)
  • At least two fire escape bed lifts are required for premises with more than one storey; minimum platform size 2.8 m (depth) × 1.8 m (width); protected lobby ≥5 m × 4 m.

    CriticalCl.9.3.2b.(6)
  • Each patient accommodation ward: max floor area 750 m² and max occupant load 75 persons (based on 10 m²/person AFA); sprinkler-protected compartment may be up to 2100 m².

    CriticalCl.9.3.2b.(5)
  • Workers' dormitory: each bedroom must not exceed 120 m² and occupant load 20 persons; occupant load basis 4.2 m²/person; at least two independent exit staircases per storey.

    CriticalCl.9.3.3
  • Temporary workers' quarters must not be located higher than 10 m above fire engine access road level or lower than first basement level; hot work is prohibited in occupied basements.

    ImportantCl.9.3.4a
  • Exit door min clear width for hospitals is 1.2 m; wards with occupant load >50 persons require at least two remotely located exits.

    ImportantCl.9.3.2b.(2)–(3)

Compliance thresholds

ParameterValueConditionClause
Max non-compartmented AFA triggering sprinkler requirement750 m²Healthcare occupancy with patient accommodationCl.9.3.2a.(3)
Min exit door clear width (hospital)1.2 mHospitalsCl.9.3.2b.(2)
Ward size requiring two exits (occupant load trigger)>50 personsPatient accommodation wardCl.9.3.2b.(3)
Max patient ward floor area (non-sprinkler)750 m²Per patient accommodation wardCl.9.3.2b.(5)(a)
Max patient ward occupant load75 persons (10 m²/person AFA)Per patient accommodation wardCl.9.3.2b.(5)(a)
Max patient ward fire compartment (sprinkler-protected)2100 m²Sprinkler-protected premisesCl.9.3.2b.(5)(c)
Smoke-free lobby min clear space (patient evacuation)6 m²Smoke-free lobby serving patient accommodation floorCl.9.3.2b.(9)(b)
Fire escape bed lift platform size2.8 m (depth) × 1.8 m (width)Fire escape bed lift clear platformCl.9.3.2b.(6)(c)
Protected lobby for fire escape bed lift5 m (length) × 4 m (width)Lobby serving fire escape bed lift and protected exit staircaseCl.9.3.2b.(6)(c)
Max dormitory bedroom floor area120 m²Workers' dormitory bedroomCl.9.3.3a
Max dormitory bedroom occupant load20 personsWorkers' dormitory bedroomCl.9.3.3a
Dormitory occupant load basis4.2 m²/personWorkers' dormitoryCl.9.3.3b
Max height of temporary workers' quarters above fire engine access road10 mTemporary workers' quarters in uncompleted buildingsCl.9.3.4a.(1)
Emergency power supply duration (temporary workers' quarters)2 hoursAll firefighting systems serving temporary workers' quartersCl.9.3.4e.(1)

Interactive decision tree

Start

What type of PG III occupancy is being assessed?