Digital Compliance Tool

SCDF Fire Code 2023 Decision Workflows

Search by clause, browse all 11 chapters, and use structured decision trees to understand the compliance path before confirming with the official SCDF code and your Qualified Person.

Beta Navigation Aid

This viewer is an interpretive workflow tool. It supports fire safety planning, but it does not replace the official Fire Code, SCDF circulars, or professional judgement.

Read the launch note

Chapter 7

Mechanical Ventilation & Smoke Control Systems

Chapter 7 governs the design, installation and maintenance of air-conditioning, mechanical ventilation, pressurisation and smoke control systems in buildings to limit fire and smoke spread and to maintain tenable conditions for evacuation and firefighting. It sets out ductwork construction rules, fire damper requirements, special ventilation requirements for exits and protected spaces, pressurisation performance criteria, smoke extraction and purging system designs, and mandatory redundancy provisions for all critical life-safety ventilation systems.

Scope: All buildings (except PG I where explicitly exempted) that incorporate air-conditioning or mechanical ventilation systems, pressurised exit staircases or corridors, or engineered smoke control systems. Specific clauses apply to hotels, car parks, kitchens, battery rooms, and buildings with large or basement compartments.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • An engineered smoke control system is required when any compartment floor area exceeds 5,000 m², total basement aggregate floor area exceeds 2,000 m² (subject to exemptions), or where atrium compartmentation is relaxed.

    CriticalClause 7.4.1a
  • The building must be sprinkler-protected when an engineered smoke control system is installed.

    CriticalClause 7.4.5b
  • The minimum clear smoke-free layer height shall be 2.5 m above floor level to maintain escape conditions.

    CriticalClause 7.4.5e
  • Smoke reservoirs for smoke removed from the room of origin must not exceed 2,000 m² (natural) or 2,600 m² (mechanical). For circulation/atrium spaces, limits are 1,000 m² (natural) and 1,300 m² (mechanical). Maximum reservoir length is 60 m.

    CriticalClause 7.4.5f
  • Smoke ventilation system must become fully operational within 60 seconds of activation.

    CriticalClause 7.4.5p
  • Fans must be capable of operating at 250°C for 2 hours. Emergency standby fan (N+1) must be provided and auto-activates if duty fan fails.

    CriticalClauses 7.4.5m, 7.5.1a
  • Smoke purging system rate shall be at least 9 ACH. Jet fan car park system requires at least 12 ACH (or not less than 9 ACH if CFD fire modelling demonstrates acceptance criteria).

    ImportantClauses 7.4.3b, 7.4.4g(1)

Compliance thresholds

ParameterValueConditionClause
Compartment floor area triggering engineered smoke controlExceeds 5,000 m²Any compartment in a building or part thereofClause 7.4.1a(2)
Total basement aggregate floor area triggering engineered smoke controlExceeds 2,000 m²Total of all basement storeys (subject to exemptions)Clause 7.4.1a(3)
Smoke vent aggregate effective openingNot less than 2.5% of floor area servedSmoke vents required in basementsClause 7.4.2a
Smoke purging rateAt least 9 ACHSmoke purging systemClause 7.4.3b
Smoke purging exhaust duct steel thickness1.2 mm (heavy gauge steel)Exhaust ducts of smoke purging and jet fan systemsClause 7.4.3g
Smoke purging exhaust fan operating temperature/duration250°C for 2 hoursSmoke purging exhaust fanClause 7.4.3h
Jet fan car park zone sizeNot larger than 2,000 m² (excluding plant rooms and circulation)Each smoke control zone in basement car parkClause 7.4.4c(1)
Jet fan — minimum headroom3 mInstallation of jet fan system in car parkClause 7.4.4d(4)
Car park exhaust rate (jet fan system)At least 12 ACH (minimum 9 ACH with CFD modelling)Car park during fire condition — jet fan systemClause 7.4.4g(1)
Jet fan maximum inlet air speed (supply air)2 m/sTo prevent recirculation of smokeClause 7.4.4f(1)
Air velocity in escape routes (jet fan car park)Not exceed 5 m/sEscape routes and ramps in car park with jet fansClause 7.4.4f(2)
Car park jet fan supply/exhaust louver separationAt least 5 m apartSupply and exhaust louvers, especially on same façadeClause 7.4.4f(3)
Minimum smoke layer base height2.5 m above floor levelDesign smoke layer base — engineered smoke control systemClause 7.4.5e
Smoke reservoir — max area (room of origin, natural)2,000 m²Natural smoke ventilation, smoke from room of originClause 7.4.5f(2)(a)
Smoke reservoir — max area (room of origin, mechanical)2,600 m²Mechanical smoke ventilation, smoke from room of originClause 7.4.5f(2)(b)
Smoke reservoir — max area (circulation/atrium, natural)1,000 m²Natural smoke ventilation, circulation or atrium spaceClause 7.4.5f(3)(a)
Smoke reservoir — max area (circulation/atrium, mechanical)1,300 m²Mechanical smoke ventilation, circulation or atrium spaceClause 7.4.5f(3)(b)
Smoke reservoir maximum length60 mAny smoke reservoirClause 7.4.5f(4)
Smoke ventilation system operational time from activationNot exceeding 60 secondsAny smoke ventilation zoneClause 7.4.5p
Fan operating temperature/duration — engineered system250°C for 2 hoursAll fans in engineered smoke control systemClause 7.4.5m(2)
Maximum smoke mass flow175 kg/sSmoke ventilation system practical limitClause 7.4.5h(1)
Minimum smoke layer temperature above ambient18°C above ambientSmoke layer temperature for smoke ventilation systemClause 7.4.5h(2)
Replacement air discharge velocityNot exceeding 5 m/sTo prevent hindrance to escapeesClause 7.4.5i(2)
Replacement air — discharge level below smoke layerAt least 1.5 m beneath smoke layerReplacement air discharge to prevent foggingClause 7.4.5i(4)
Replacement air intake separation from exhaustAt least 5 mReplacement air intake sitingClause 7.4.5i(3)

Interactive decision tree

Start

Determine if smoke control provisions are required for this building.