Chapter 6

Firefighting Systems

Chapter 6 specifies the full range of active firefighting systems required in Singapore buildings under the SCDF Code of Practice for Fire Precautions in Buildings 2023. It covers portable extinguishers, rising main and hose reel systems, electrical fire alarm systems (including HFAD for residential units), automatic fire sprinkler installations, fixed automatic extinguishing systems, lift provisions (fire lifts and evacuation lifts), colour identification of fire protection equipment, and redundancy requirements for fire pumping systems. Key decision triggers are building habitable height (thresholds at 10 m, 24 m, 60 m) and purpose group, which together determine the type of rising main, whether sprinklers are mandatory, the number of fire lifts required, and the class of fire alarm system.

Scope: All new and existing buildings in Singapore across Purpose Groups I–VIII, with specific applicability thresholds by building height, floor area, occupancy type, and basement depth. Applies to Qualified Persons, building owners, and fire safety engineers.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Dry rising mains required for PG II–VIII buildings with habitable height > 10 m and ≤ 60 m; wet rising mains required for habitable height > 60 m.

    CriticalClause 6.2.1a
  • Dry rising mains (SS 575) must be provided to supply any part of a single or multiple level basement regardless of other rising main provisions.

    CriticalClause 6.2.1b
  • All buildings fitted with rising mains must have a fire engine accessway/road within 18 m of the breeching inlet, and inlets must be visible from the accessway.

    CriticalClause 6.2.3a
  • Standby fire hoses (63.5 mm nominal diameter, 30 m length, Dutch Roll, Type 3 per BS 6391) are required for every rising main except in PG II buildings. Hose must be located ≤ 2 m from landing valve.

    ImportantClause 6.2.5
  • Hose reels (SS 575) must be provided on every storey of every building regardless of height; coverage distance is 36 m (30 m hose path + 6 m throw). Reels must be ≤ 5 m from exit door.

    CriticalClause 6.2.8a.(1), 6.2.8d.(2)
  • Wet riser pumps must be installed within a fire-compartmented pump room; pump room floor level must not be lower than main floor level.

    ImportantClause 6.2.4f
  • Height measurement for rising main classification is taken from the fire engine accessway level (or access road where no accessway exists).

    ImportantClause 6.2.1c

Compliance thresholds

ParameterValueConditionClause
Habitable height — dry rising main trigger (lower bound)> 10 mPG II to VIII buildingsClause 6.2.1a.(1)
Habitable height — dry rising main upper bound / wet rising main trigger≤ 60 m for dry; > 60 m for wetPG II to VIII buildingsClause 6.2.1a.(1)–(2)
Fire engine accessway distance to breeching inlet≤ 18 mAll buildings fitted with rising mainsClause 6.2.3a
1st storey landing valve — distance from breeching inlet triggering additional valve> 38 m (30 m hose + 8 m jet throw)PG III–VIII buildings (not PG II)Clause 6.2.2c.(1)
Hose reel coverage distance36 m (30 m hose path + 6 m throw)All storeysClause 6.2.8d.(2)
Hose reel siting distance from exit door≤ 5 mAll hose reelsClause 6.2.8d.(2)
Standby hose reel nominal diameter20 mm or 25 mmAll hose reelsClause 6.2.8b
Standby hose reel maximum length≤ 30 mAll hose reelsClause 6.2.8b
Standby fire hose nominal diameter63.5 mmRising main standby hoses (all except PG II buildings)Clause 6.2.5a.(1)
Standby fire hose standard length30 mEach standby fire hoseClause 6.2.5a.(3)
Standby hose coupling minimum working pressure15 barCouplings on standby fire hosesClause 6.2.5a.(2)
Water flow rate — wet riser, 1 stack (non-residential)38 L/sNon-residential buildings, 1 stackClause 6.2.4g Table 6.2.4g
Water flow rate — wet riser, 1 stack (residential)27 L/sResidential buildings, 1 stackClause 6.2.4g Table 6.2.4g
Water flow rate — wet riser, 4+ stacks (non-residential)95 L/sNon-residential buildings, 4 or more stacksClause 6.2.4g Table 6.2.4g
Foam inlet breeching pipe bore (minimum)100 mmBasement boiler/storage rooms not easily accessible for firefightingClause 6.2.7b
Hose reel cabinet depth (one hose)≤ 250 mmWall-mounted cabinets for one fire hoseClause 6.2.5c.(5)
Hose reel cabinet depth (two hoses)≤ 350 mmWall-mounted cabinets for two fire hosesClause 6.2.5c.(5)
Hose reel siting from landing valve≤ 2 mStandby fire hose adjacent to landing valveClause 6.2.5b.(1)
Non-residential hose reel exemption — AFA threshold≤ 150 m²Non-residential unit at 1st storey of mixed commercial-residential or single-storey standalone buildingClause 6.2.8a.(3)(b)(i)

Interactive decision tree

DecisionClause 6.2.1a, 6.2.1c

What is the habitable height of the building (measured from fire engine accessway level)?