Chapter 6

Firefighting Systems

Chapter 6 specifies the full range of active firefighting systems required in Singapore buildings under the SCDF Code of Practice for Fire Precautions in Buildings 2023. It covers portable extinguishers, rising main and hose reel systems, electrical fire alarm systems (including HFAD for residential units), automatic fire sprinkler installations, fixed automatic extinguishing systems, lift provisions (fire lifts and evacuation lifts), colour identification of fire protection equipment, and redundancy requirements for fire pumping systems. Key decision triggers are building habitable height (thresholds at 10 m, 24 m, 60 m) and purpose group, which together determine the type of rising main, whether sprinklers are mandatory, the number of fire lifts required, and the class of fire alarm system.

Scope: All new and existing buildings in Singapore across Purpose Groups I–VIII, with specific applicability thresholds by building height, floor area, occupancy type, and basement depth. Applies to Qualified Persons, building owners, and fire safety engineers.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Pumping systems for wet rising mains, hose reels, sprinklers and hydrants must each have redundancy so performance is unaffected when any single pump or control system is out of service.

    CriticalClause 6.8
  • Redundancy applies equally to routine maintenance outages and breakdown scenarios — the system must remain fully operational with one pump out.

    CriticalClause 6.8
  • Combined sprinkler and wet riser tank systems must have separate pump sets to allow simultaneous operation of both systems (complementing the redundancy requirement).

    ImportantClause 6.4.8c
  • Pump room must be fire-compartmented and pump room floor level must not be lower than the main floor level (applies to both sprinkler and wet riser pump rooms).

    ImportantClause 6.2.4f, 6.4.3b

Interactive decision tree

DecisionClause 6.8

Does the building have any of the following: wet rising main, hose reel system, sprinkler system, or private fire hydrant system?