Chapter 6

Firefighting Systems

Chapter 6 specifies the full range of active firefighting systems required in Singapore buildings under the SCDF Code of Practice for Fire Precautions in Buildings 2023. It covers portable extinguishers, rising main and hose reel systems, electrical fire alarm systems (including HFAD for residential units), automatic fire sprinkler installations, fixed automatic extinguishing systems, lift provisions (fire lifts and evacuation lifts), colour identification of fire protection equipment, and redundancy requirements for fire pumping systems. Key decision triggers are building habitable height (thresholds at 10 m, 24 m, 60 m) and purpose group, which together determine the type of rising main, whether sprinklers are mandatory, the number of fire lifts required, and the class of fire alarm system.

Scope: All new and existing buildings in Singapore across Purpose Groups I–VIII, with specific applicability thresholds by building height, floor area, occupancy type, and basement depth. Applies to Qualified Persons, building owners, and fire safety engineers.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • A fixed automatic fire extinguishing system not required by the Code cannot be used as a substitute for any Code-required provision unless specifically approved by SCDF.

    CriticalClause 6.5.1
  • Such systems must not adversely affect the performance of the Code-prescribed firefighting systems already required.

    ImportantClause 6.5.1
  • Design and installation must comply with Codes of Practice acceptable to the SCDF (e.g. SS CP 52 for sprinklers, NFPA 12 for CO2, NFPA 2001 for clean agents).

    ImportantClause 6.5.2
  • For data centres/comms rooms using clean agent in lieu of sprinklers, the enclosure requires 1-hr fire resistance, 1-hr fire door, ≤2 exits, ≤15 m direct travel to exit door, and clean agent conforming to Cl.6.5.2.

    CriticalClause 6.4.4c

Compliance thresholds

ParameterValueConditionClause
Clean agent room — fire resistance rating1 hourEnclosure substituting sprinklers with clean agent (data centres/comms rooms)Clause 6.4.4c.(1)
Clean agent room — maximum exits≤ 2 exitsClean agent enclosureClause 6.4.4c.(3)
Clean agent room — maximum direct travel distance to exit≤ 15 mClean agent enclosureClause 6.4.4c.(4)

Interactive decision tree

DecisionClause 6.5.1

Is the fixed automatic fire extinguishing system proposed as a substitute for a Code-required provision (e.g. replacing mandatory sprinklers)?