Chapter 6
Firefighting Systems
Chapter 6 specifies the full range of active firefighting systems required in Singapore buildings under the SCDF Code of Practice for Fire Precautions in Buildings 2023. It covers portable extinguishers, rising main and hose reel systems, electrical fire alarm systems (including HFAD for residential units), automatic fire sprinkler installations, fixed automatic extinguishing systems, lift provisions (fire lifts and evacuation lifts), colour identification of fire protection equipment, and redundancy requirements for fire pumping systems. Key decision triggers are building habitable height (thresholds at 10 m, 24 m, 60 m) and purpose group, which together determine the type of rising main, whether sprinklers are mandatory, the number of fire lifts required, and the class of fire alarm system.
Scope: All new and existing buildings in Singapore across Purpose Groups I–VIII, with specific applicability thresholds by building height, floor area, occupancy type, and basement depth. Applies to Qualified Persons, building owners, and fire safety engineers.
Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.
Critical points
PG III–VIII buildings with total floor area per storey exceeding Table 6.3A thresholds must have an electrically supervised fire alarm system per SS 645. Buildings of 2–4 storeys with floor area exceeding Table 3.2A column (2) must have an automatic fire alarm.
CriticalClause 6.3.1aPG III–VIII buildings without stay-in facilities: single storey >400 m² and 2–4 storey >200 m² require manual alarm; buildings >4 storeys require automatic + manual alarm regardless of area.
CriticalClause 6.3.1a, Table 6.3AAll individual residential units (PG I and II) must be fitted with Home Fire Alarm Devices (HFAD) complying with Cl.6.3.6. Single-storey homes require minimum 1 smoke detector; multi-storey homes require minimum 1 per storey (2+ if circulation area >70 m²).
CriticalClause 6.3.6Healthcare, hotels, oil refineries, warehouses, theatres, and all buildings with mandatory automatic suppression or alarm systems must connect the fire alarm to the SCDF Operations Centre via an approved alarm monitoring company.
CriticalClause 6.3.8Manual call points must be placed such that no person travels more than 30 m from any position to activate the alarm. Height: 800 mm–1.2 m above finished floor level.
ImportantClause 6.3.3a, 6.3.3cVideo Image Fire Detection Systems (VIFDS) must be installed in addition to electrical fire alarm systems for unmanned PG III–VIII buildings with internal open space >2000 m² or ceiling height >12 m that require automatic fire alarm.
ImportantClause 6.3.11Visual alarms (flashing beacon/strobe, 30–130 flashes/min, white or red, 2–3 m AFF) must be provided in addition to audible alarms in toilets/full-height cubicles, car park floors, lift lobbies, and entertainment areas.
ImportantClause 6.3.5c
Compliance thresholds
| Parameter | Value | Condition | Clause |
|---|---|---|---|
| Floor area triggering manual fire alarm — PG III–VIII (no stay-in), single storey | > 400 m² | Single-storey PG III–VIII buildings without stay-in facilities | Table 6.3A |
| Floor area triggering manual fire alarm — PG III–VIII (no stay-in), 2–4 storeys | > 200 m² per storey | 2–4 storey PG III–VIII buildings without stay-in facilities | Table 6.3A |
| Storey count triggering automatic + manual fire alarm — PG III–VIII (no stay-in) | > 4 storeys | PG III–VIII buildings without stay-in facilities | Table 6.3A |
| Manual call point travel distance | ≤ 30 m | Any position within building to nearest call point | Clause 6.3.3a |
| Manual call point mounting height | 800 mm – 1.2 m above FFL | All manual call points | Clause 6.3.3c |
| Alarm sounder minimum sound level | 65 dBA or 5 dBA above ambient (whichever is greater), ≤ 120 dBA | PG II mixed occupancy — non-residential units and adjacent residential floors | Clause 6.3.1b.(1) |
| Visual alarm mounting height | 2 m – 3 m above FFL | All visual alarms | Clause 6.3.5c.(3) |
| Visual alarm flash rate | 30 – 130 flashes per minute | All visual alarm devices | Clause 6.3.5c.(4)(d) |
| HFAD battery minimum life | ≥ 10 years | HFAD powered by built-in battery | Clause 6.3.6a.(6) |
| HFAD — minimum detectors for single-storey home | 1 smoke detector | Single-storey HDB flats, apartments, condominiums, and landed dwellings | Clause 6.3.6c, Table 6.3.6 |
| HFAD — minimum detectors for multi-storey home | 1 smoke detector per storey | Multi-storey homes | Clause 6.3.6c, Table 6.3.6 |
| HFAD — extra detector threshold for multi-storey circulation area | > 70 m² | Circulation area on any storey of multi-storey home requires ≥ 2 detectors on that storey | Table 6.3.6 |
| VIFDS trigger — internal open space | > 2000 m² | Unmanned PG III–VIII building requiring automatic fire alarm | Clause 6.3.11a.(2) |
| VIFDS trigger — ceiling height | > 12 m | Unmanned PG III–VIII building requiring automatic fire alarm | Clause 6.3.11a.(2) |