Digital Compliance Tool

SCDF Fire Code 2023 Decision Workflows

Search by clause, browse all 11 chapters, and use structured decision trees to understand the compliance path before confirming with the official SCDF code and your Qualified Person.

Beta Navigation Aid

This viewer is an interpretive workflow tool. It supports fire safety planning, but it does not replace the official Fire Code, SCDF circulars, or professional judgement.

Read the launch note

Chapter 6

Firefighting Systems

Chapter 6 specifies the full range of active firefighting systems required in Singapore buildings under the SCDF Code of Practice for Fire Precautions in Buildings 2023. It covers portable extinguishers, rising main and hose reel systems, electrical fire alarm systems (including HFAD for residential units), automatic fire sprinkler installations, fixed automatic extinguishing systems, lift provisions (fire lifts and evacuation lifts), colour identification of fire protection equipment, and redundancy requirements for fire pumping systems. Key decision triggers are building habitable height (thresholds at 10 m, 24 m, 60 m) and purpose group, which together determine the type of rising main, whether sprinklers are mandatory, the number of fire lifts required, and the class of fire alarm system.

Scope: All new and existing buildings in Singapore across Purpose Groups I–VIII, with specific applicability thresholds by building height, floor area, occupancy type, and basement depth. Applies to Qualified Persons, building owners, and fire safety engineers.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Extinguishers are required in all buildings except PG I, residential floors of PG II, standalone or mixed-use residential car parking areas, and specific low-height roof PV installations.

    CriticalClause 6.1.2a
  • All extinguishers must be constructed to SS EN 3 and charged, tested, maintained and tagged in accordance with SS 578.

    CriticalClause 6.1.1
  • Classification of extinguisher type must be selected per SS 578 to suit the nature of processes and contents of the building; size, quantity and siting must comply with SS 578 for the relevant occupancy hazard class.

    ImportantClause 6.1.3
  • Where a roof level is a non-habitable floor, extinguishers must still be provided to cover M&E plant and equipment.

    ImportantClause 6.1.2b
  • Extinguishers must be installed and conspicuously marked per SS 578.

    NoteClause 6.1.4

Compliance thresholds

ParameterValueConditionClause
Roof height — exemption from extinguisher requirement (single-storey building, accessible roof)≤ 12 mRoof used solely for PV installations per Cl.10.2.1b.(1)Clause 6.1.2a.(4)
Roof height — exemption (inaccessible pitched roof)≤ 24 m from grade levelRoof used solely for PV installations per Cl.10.2.1b.(1)Clause 6.1.2a.(4)
Clear width of external overhead bridge/shed — exemption threshold< 6 mOpen-sided overhead bridge/shed used solely for roof-mounted PV installationsClause 6.1.2a.(5)

Interactive decision tree

DecisionClause 6.1.2a.(1)

Is the building Purpose Group I (private dwellings)?