Chapter 5

Electrical Power Supplies

Chapter 5 governs the electrical power supply requirements for fire safety systems in buildings, covering both primary and secondary (standby) power sources. It mandates that all fire-related electrical systems — including fire alarms, emergency lighting, wet rising mains, sprinklers, mechanical ventilation/pressurisation, and emergency generators — must have secondary power supplies sized and installed to the relevant Singapore Standards. The chapter also sets requirements for fire-resistant cables, motor control equipment, and outdoor emergency generator fuel containment.

Scope: All buildings in Singapore where fire safety electrical systems are required by the SCDF Code of Practice or other Codes/Regulations, including buildings with fire lifts, fire alarm systems, emergency lighting, wet rising mains, sprinkler systems, mechanical ventilation/pressurisation for fire safety, and emergency generators.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • All emergency generators used as secondary power supply must comply with SS 535.

    CriticalClause 5.2.4a
  • Outdoor emergency generator day tanks must be double-skin steel construction OR have an internal bund wall capable of containing 100% of the diesel in the day tank. The generator enclosure must also be able to contain any diesel leakage.

    CriticalClause 5.2.4b.(1) & (2)
  • Maximum diesel quantity permitted in an outdoor emergency generator's day tank is 1000 litres.

    CriticalClause 5.2.4b.(3)

Compliance thresholds

ParameterValueConditionClause
Max diesel in outdoor emergency generator day tank1000 litresOutdoor emergency generator day tankClause 5.2.4b.(3)
Internal bund containment capacity100% of day tank diesel contentWhere internal bund (alternative to double-skin) is usedClause 5.2.4b.(2)

Interactive decision tree

Start

Is an emergency generator provided as a secondary power source for fire safety systems?