Chapter 3
Structural Fire Precautions
Chapter 3 sets out requirements to prevent fire spreading between adjoining buildings, ensure structural stability during fire, and limit fire spread within a building through compartmentation. It specifies fire resistance ratings for structural elements by purpose group and building dimensions, governs the design of compartment walls and floors, protected shafts, external walls, and fire-stopping. It also regulates surface spread of flame for internal finishes and roof coverings, and prescribes material standards for construction elements.
Scope: All buildings covered by the SCDF Fire Code unless otherwise exempted; specific provisions vary by Purpose Group (PG I–VIII), building height, floor area, cubical extent, sprinkler protection status, and location relative to lot boundaries.
Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.
Critical points
Exit staircases, exit passageways, and smoke-free/fire lift lobbies require Class 0 (BS) or Class B (EN) wall and ceiling surfaces in ALL buildings regardless of sprinkler protection.
CriticalCl.3.13.4a, Table 3.13AComposite panels used as external wall cladding must be mounted against a 1-hr fire-rated wall and the core material must meet at least BS 476 Part 4 / BS 476 Part 11 / Class 0 (BS) / Class B (EN), or the panel assembly must comply with NFPA 285.
CriticalCl.3.15.13cPlastics in walls, ceilings, floors, and roofs are generally prohibited unless they comply with Cl.3.15.19 fire test requirements. Plastics are NOT permitted in exit staircases or exit passageways.
CriticalCl.3.15.15, Cl.3.15.19Roof covering surface spread of flame must be at least Class 1 or ASTM Class A except for PG I/II buildings and sprinkler-protected buildings. Composite panel roofs must comply with Table 3.13B.
ImportantCl.3.14.1Intumescent paint for structural steel protection must comply with BS 8202: Part 2 weathering tests; post-weather fire resistance must not diminish more than 25%. A mandatory information sign must be affixed at a conspicuous location.
ImportantCl.3.15.2Fire-rated glass may only be used for compartment walls, floors, and protected shaft enclosures in sprinkler-protected buildings, and must comply with BS 476: Part 20–23 (stability, integrity, insulation) and impact performance requirements.
ImportantCl.3.15.14UPVC window frames must be listed under the product listing scheme and comply with Table 3.15.20 installation height, window length, and masonry break conditions per building type.
NoteCl.3.15.20, Table 3.15.20
Compliance thresholds
| Parameter | Value | Condition | Clause |
|---|---|---|---|
| Minimum surface flame spread — exit staircases and exit passageways (all buildings) | Class 0 (BS) / Class B (EN) | All buildings including sprinkler-protected; exit staircases, exit passageways, smoke-free/fire lift lobbies | Table 3.13A |
| Minimum surface flame spread — circulation spaces (PG III–VIII, non-sprinkler) | Class 0 (BS) / Class B (EN) | Corridors, passageways in non-sprinkler PG III–VIII buildings | Table 3.13A |
| Minimum surface flame spread — rooms in PG III–VIII non-sprinkler buildings | Class 1 (BS) / Class C (EN) | Rooms and compartments in PG III, IV, V, VI, VII, VIII non-sprinkler buildings | Table 3.13A |
| Permitted Class 3 (not lower) wall area in PG III room/compartment | Max 20 m² | Part of wall surface in PG III building or compartment may be Class 3 if total area ≤20 m² | Cl.3.13.5a.(1) |
| Permitted Class 3 (not lower) wall area in other PG room/compartment | Max 60 m² | Part of wall surface in PG other than III may be Class 3 if total area ≤60 m² | Cl.3.13.5a.(2) |
| Thin wall/ceiling finishes (≤1 mm) on non-combustible substrate — flame spread exemption | 1 mm maximum thickness | Thin sheet not exceeding 1 mm on non-combustible substrate is exempt from flame spread requirements (not for exit staircases/passageways) | Cl.3.13.6 |
| Roof covering minimum flame spread (non-PG I/II, non-sprinkler buildings) | Class 1 (BS 476 Part 7) or ASTM Class A | Surface of roof covering and roof construction for buildings other than PG I, PG II, and non-sprinkler | Cl.3.14.1a |
| UPVC window frame — installation height limit (PG II, non-sprinkler) | < 60 m from fire engine access level | PG II non-sprinkler-protected building | Table 3.15.20 |
| UPVC window frame — max horizontal length (PG II) | < 3 m | PG II buildings (both sprinkler and non-sprinkler) | Table 3.15.20 |
| Intumescent paint post-weathering fire resistance reduction limit | Max 25% reduction | Intumescent paint applied to structural steel; fire resistance rating after weathering tests must not diminish more than 25% | Cl.3.15.2b |
| Toilet cubicle partition — Class 3 total exposed area limit | Max 60 m² | Class 3 surface material for toilet cubicle partitions; total exposed surface in the toilet must not exceed 60 m² | Cl.3.15.17 |