Chapter 3
Structural Fire Precautions
Chapter 3 sets out requirements to prevent fire spreading between adjoining buildings, ensure structural stability during fire, and limit fire spread within a building through compartmentation. It specifies fire resistance ratings for structural elements by purpose group and building dimensions, governs the design of compartment walls and floors, protected shafts, external walls, and fire-stopping. It also regulates surface spread of flame for internal finishes and roof coverings, and prescribes material standards for construction elements.
Scope: All buildings covered by the SCDF Fire Code unless otherwise exempted; specific provisions vary by Purpose Group (PG I–VIII), building height, floor area, cubical extent, sprinkler protection status, and location relative to lot boundaries.
Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.
Critical points
Cavity barriers must provide at least ½-hr fire resistance and must extend the full cavity to close edges of cavities and sub-divide them at compartment/separating wall/floor junctions.
CriticalCl.3.11.3, Cl.3.11.5Exit passageways, smoke-free lobbies, fire lift lobbies, and exit staircases: suspended ceiling over these areas must have non-combustible supporting elements and ceiling, and exposed surfaces must be Class 0 flame spread. Cavity barriers cannot be omitted here even in sprinkler-protected buildings.
CriticalCl.3.11.11Raised floors: concealed space must not be used for storage; supporting structure must be non-combustible with melting point ≥750°C; maximum unobstructed area in the concealed space must not exceed 930 m² (cavity barriers required).
ImportantCl.3.11.8For non-sprinkler buildings: if raised floor cavity height exceeds 150 mm, an automatic smoke detection system (SS 645) is required. For sprinkler buildings: detection required if 150–400 mm; sprinkler required if >400 mm.
ImportantCl.3.11.8kFire-stopping materials must have the necessary fire resistance when tested to BS 476: Part 20; all gaps around pipe/duct/conduit/cable penetrations in compartment elements must be filled with approved fire-stopping material.
CriticalCl.3.12.1, Cl.3.12.2PG I buildings and residential units in PG II buildings are exempt from cavity barrier requirements in concealed floor and ceiling spaces.
NoteCl.3.11.12
Compliance thresholds
| Parameter | Value | Condition | Clause |
|---|---|---|---|
| Maximum cavity dimension — between roof and ceiling (PG I & II) | No limit | Cavity between roof and ceiling in PG I or II buildings | Table 3.11A |
| Maximum cavity dimension — between roof and ceiling (other PGs) | 20 m | Cavity between roof and ceiling in any PG other than I or II | Table 3.11A |
| Maximum cavity dimension — any other cavity with Class 0 surface exposed | 20 m | Any cavity other than roof/ceiling cavity where exposed surfaces are Class 0 | Table 3.11A |
| Maximum cavity dimension — any other cavity with non-Class 0 surface | 8 m | Any cavity other than roof/ceiling cavity where exposed surfaces are not Class 0 | Table 3.11A |
| Cavity barrier minimum fire resistance | ½ hr | All cavity barriers | Cl.3.11.5a |
| Maximum unobstructed area in raised floor concealed space requiring cavity barriers | 930 m² | Raised floors with or without accessible panels (non-sprinkler protected) | Cl.3.11.8i |
| Raised floor cavity height triggering smoke detection (non-sprinkler building) | > 150 mm | Non-sprinkler-protected building raised floor cavity height exceeding 150 mm | Cl.3.11.8k |
| Raised floor cavity height triggering automatic sprinkler (sprinkler building) | > 400 mm | Sprinkler-protected building raised floor cavity height exceeding 400 mm | Cl.3.11.8k |
| Suspended ceiling cavity exempt from cavity barriers (detector-protected building, no detection in cavity) | ≤ 800 mm depth | Detector-protected building, suspended ceiling cavity depth does not exceed 800 mm | Cl.3.11.9d |
| Suspended ceiling cavity exempt from cavity barriers (sprinkler-protected, no combustibles) | ≤ 800 mm depth | Sprinkler-protected building, concealed space 400–800 mm deep with no combustible materials | Cl.3.11.9e |
Interactive decision tree
Cavity Barrier and Fire-Stopping Requirement Check