Chapter 2

Means of Escape

Chapter 2 governs the design, construction, and maintenance of all exit facilities required to provide safe means of escape from buildings in Singapore. It covers how to determine exit requirements based on occupancy type, occupant load, travel distance, and exit capacity, and sets specific numeric thresholds drawn from Table 2.2A. Special provisions address smoke-free approaches to staircases, exit door requirements, remoteness of exits, and dedicated requirements for persons with disabilities (PWDs).

Scope: Applies to all buildings erected, altered, or changed in occupancy in Singapore, across all purpose groups (PG I–VIII). Specific sub-clauses address residential, commercial, industrial, healthcare, assembly, and basement occupancies.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Maximum travel distance is measured from a point 400 mm from enclosure walls of the room or space to the nearest exit. Never measure from the furthest corner.

    ImportantClause 2.2.6c
  • For large open floor areas without sub-division, the 'direct distance' concept may be used, but shall not exceed two-thirds of the maximum permitted travel distance in Table 2.2A.

    ImportantClause 2.2.6b
  • One-way (dead-end) travel distance from the most remote point to the splitting point must not exceed the one-way travel limit in Table 2.2A. At the splitting point, the angle of divergence between any two routes must be ≥ 90°.

    CriticalClause 2.3.12e
  • High hazard occupancies have the shortest travel distances (10 m one-way / 20 m two-way non-sprinklered; 20 m / 35 m sprinklered) and must be treated with particular care.

    CriticalTable 2.2A
  • Healthcare (inpatient) occupancies have very short two-way travel distances (30 m non-sprinklered / 45 m sprinklered) and very restrictive dead-end limits (15 m).

    CriticalTable 2.2A
  • Residential apartment/maisonette travel distance is determined per Cl.9.2.1a(5), not measured from the unit entrance.

    ImportantClause 2.2.6d; Table 2.2A Note (k)

Compliance thresholds

ParameterValueConditionClause
Max travel distance — High hazard, one-way, non-sprinklered10 mHigh hazard occupancy, non-sprinklered, single direction to exitTable 2.2A
Max travel distance — High hazard, one-way, sprinklered20 mHigh hazard occupancy, sprinklered, single direction to exitTable 2.2A
Max travel distance — High hazard, two-way, non-sprinklered20 mHigh hazard occupancy, non-sprinklered, two exits availableTable 2.2A
Max travel distance — High hazard, two-way, sprinklered35 mHigh hazard occupancy, sprinklered, two exits availableTable 2.2A
Max travel distance — Industrial (factories/workshops/godowns), one-way, non-sprinklered15 mIndustrial buildings, non-sprinklered, single direction to exitTable 2.2A
Max travel distance — Industrial, two-way, non-sprinklered30 mIndustrial buildings, non-sprinklered, two exitsTable 2.2A
Max travel distance — Industrial, two-way, sprinklered60 mIndustrial buildings, sprinklered, two exitsTable 2.2A
Max travel distance — Shops/Healthcare outpatient, two-way, non-sprinklered45 mShops or healthcare outpatient, non-sprinkleredTable 2.2A
Max travel distance — Offices, two-way, non-sprinklered45 mOffices, non-sprinkleredTable 2.2A
Max travel distance — Offices, two-way, sprinklered75 mOffices, sprinkleredTable 2.2A
Max travel distance — Places of public resort & car parks, two-way, non-sprinklered45 mPlaces of public resort and car parks, non-sprinkleredTable 2.2A
Max travel distance — Schools, two-way, non-sprinklered45 mSchools and educational buildings, non-sprinkleredTable 2.2A
Max travel distance — Healthcare (inpatient), two-way, non-sprinklered30 mHealthcare inpatient facilities, non-sprinkleredTable 2.2A
Max travel distance — Healthcare (inpatient), two-way, sprinklered45 mHealthcare inpatient facilities, sprinkleredTable 2.2A
Max travel distance — Hotels/dormitories, two-way, non-sprinklered30 mHotels, boarding houses, serviced apartments, hostels, dormitories, non-sprinkleredTable 2.2A
Max travel distance — Hotels/dormitories, two-way, sprinklered60 mHotels, boarding houses, etc., sprinkleredTable 2.2A
Max travel distance — Blocks of flats/maisonettes, two-way, non-sprinklered30 m (single staircase blocks: per Cl.9.2.1a(8))Residential flats/maisonettes, non-sprinkleredTable 2.2A Note (g)(k)
Max dead-end (one-way) corridor — non-sprinklered15 mAll occupancies with stated dead-end limits, non-sprinkleredTable 2.2A
Max dead-end (one-way) corridor — sprinklered20 mAll occupancies with stated dead-end limits, sprinkleredTable 2.2A
Direct distance limit (open large floor areas without sub-division)2/3 of maximum travel distance per Table 2.2ALarge open floor areas without sub-division of rooms/corridorsClause 2.2.6b
Measurement start point for travel distance400 mm from enclosure wallAll travel distance calculationsClause 2.2.6c
Min corridor width — corridors/staircases/passageways (most occupancies)1.2 mCorridors, ramps, exit passageways (general); 1.5 m for school classrooms; 2 m for healthcare inpatient corridorsTable 2.2A
Exit capacity (persons per unit) — door openings, most occupancies100 persons per unit of width (500 mm)Door openings for non-high-hazard commercial/industrial occupanciesTable 2.2A
Exit capacity (persons per unit) — staircases, non-sprinklered, most occupancies60 persons per unit of width (500 mm)Staircases/exit passageways, non-sprinklered (offices, shops, schools, etc.)Table 2.2A
Exit capacity (persons per unit) — staircases, sprinklered, most occupancies100 persons per unit of width (500 mm)Staircases/exit passageways, sprinklered (offices, shops, schools, etc.)Table 2.2A

Interactive decision tree

Start

Verify travel distance compliance for each floor.