Chapter 2

Means of Escape

Chapter 2 governs the design, construction, and maintenance of all exit facilities required to provide safe means of escape from buildings in Singapore. It covers how to determine exit requirements based on occupancy type, occupant load, travel distance, and exit capacity, and sets specific numeric thresholds drawn from Table 2.2A. Special provisions address smoke-free approaches to staircases, exit door requirements, remoteness of exits, and dedicated requirements for persons with disabilities (PWDs).

Scope: Applies to all buildings erected, altered, or changed in occupancy in Singapore, across all purpose groups (PG I–VIII). Specific sub-clauses address residential, commercial, industrial, healthcare, assembly, and basement occupancies.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Internal exit staircases must be enclosed with fire-rated construction (per Cl.3.8) and have no more than two exit doors opening into the staircase shaft at each storey (excluding the final discharge door).

    CriticalClause 2.3.3a(1)
  • Basement exit staircases must NOT be continuous with staircases serving non-basement storeys, unless specifically permitted by SCDF.

    CriticalClause 2.3.5b
  • All exit staircases must discharge at ground level directly into an external space, an open-sided external corridor (≤5 m from eave line), an open-to-sky corridor of ≥1.2 m width, or a compliant air well.

    CriticalClause 2.3.3c(1)
  • Where two exits are required, separation distance measured in a straight line between the furthest edges of the exit doors must be ≥ 1/2 the maximum overall diagonal dimension of the area (or ≥ 1/3 if sprinklered), and in all cases ≥ 7 m.

    CriticalClause 2.3.12b–c
  • Exit doors and exit access doors must open in the direction of travel when leading to areas of refuge, exit enclosures, high hazard areas, or spaces with occupant load > 50 persons.

    CriticalClause 2.3.9c
  • Exit staircases in buildings with habitable height > 24 m (except PG II) must be pressurised if they cannot be naturally ventilated.

    CriticalClause 2.3.3d(8)
  • Spiral staircases may only serve as required exits if external, unenclosed, serving ≤25 persons on mezzanine floors/balconies, constructed of non-combustible materials, with tread length ≥750 mm, and not more than 10 m high.

    ImportantClause 2.3.7a
  • Exit staircase re-entry is required for non-residential buildings with exit staircases serving more than 7 storeys. Re-entry points must be ≤6 storeys apart and not more than 3 storeys above the highest re-entry door.

    ImportantClause 2.3.9l

Compliance thresholds

ParameterValueConditionClause
Staircase riser height (maximum)175 mmAll exit staircasesClause 2.3.3d(4)
Staircase tread depth — residential units≥ 225 mmWithin residential unitsClause 2.3.3d(4)(a)
Staircase tread depth — common areas of residential buildings≥ 275 mmCommon areas of residential buildingsClause 2.3.3d(4)(a)
Staircase tread depth — PG VI and VIII buildings≥ 250 mmPG VI and VIII buildingsClause 2.3.3d(4)(b)
Staircase tread depth — all other buildings≥ 275 mmAll buildings not covered by (a) or (b)Clause 2.3.3d(4)(c)
Staircase clear headroom≥ 2 mMeasured from pitch line of staircase or finished floor level of landing to underside of obstructionClause 2.3.3d(5)
Staircase ventilation opening (natural)≥ 10% of floor area per floor of the staircaseAll exit staircases (fixed openings in external walls)Clause 2.3.3d(7)
Habitable height threshold for pressurisation of internal exit staircases24 mInternal exit staircases without natural ventilation where building exceeds 24 m (except PG II)Clause 2.3.3d(8)
Spiral staircase — maximum height when used as required exit10 mSpiral staircase used as required exit (external, unenclosed, ≤25 persons)Clause 2.3.7a
Spiral staircase — tread length (minimum) when used as required exit750 mmSpiral staircase used as required exitClause 2.3.7a
Spiral staircase — maximum occupant load when used as required exit25 personsMezzanine floors, balconies, or any storeyClause 2.3.7a
Exit ramp maximum slope1 in 10All internal and external exit ramps (curved ramps: max 1 in 12)Clause 2.3.8a
Exit/exit access door maximum opening force30 N at 0°; 20 N at 30° openingAll exit doors and exit access doorsClause 2.3.9d(3)
Fire door vision panel clear size100 mm (width) × 600 mm (height)Fire door to exit staircase and smoke-free/fire lift lobbyClause 2.3.9e
Vision panel bottom edge height900 mm above finished floor levelFire door to exit staircase and smoke-free/fire lift lobbyClause 2.3.9e
Minimum exit separation distance (straight line between door edges)≥ 7 m (absolute minimum in all cases)Any two required exitsClause 2.3.12b(2)
Minimum exit separation — non-sprinklered building≥ 1/2 maximum overall diagonal dimension of area servedNon-sprinklered buildingClause 2.3.12b
Minimum exit separation — sprinklered building≥ 1/3 maximum overall diagonal dimension of area servedBuilding protected by approved automatic sprinkler systemClause 2.3.12c
Scissor staircase door separation distance≥ 7 m between closer edges of staircase doorsExit door openings of scissor exit staircasesClause 2.3.4c
Unprotected openings near staircase discharge point≥ 3 m away; reducible to 1.5 m if along same plane as staircase exitBoth internal and external exit staircases at discharge pointClause 2.3.3c(4)
Maximum discharge distance to external space (sprinklered building — covered circulation)10 mSprinklered building where up to 50% of staircases discharge to covered ground level circulationClause 2.3.3c(2)(b)
Exit passageway ventilation (natural)≥ 15% of floor area of exit passagewayInternal exit passagewaysClause 2.3.2d(1)
Staircase re-entry — maximum separation between re-entry points≤ 6 storeys apartNon-residential buildings with exit staircases serving > 7 storeysClause 2.3.9l(2)
Staircase re-entry — maximum storeys above highest re-entry door3 storeysNon-residential buildings with staircase re-entryClause 2.3.9l(2)

Interactive decision tree

Start

Design exit staircase and verify means of escape requirements.