Digital Compliance Tool

SCDF Fire Code 2023 Decision Workflows

Search by clause, browse all 11 chapters, and use structured decision trees to understand the compliance path before confirming with the official SCDF code and your Qualified Person.

Beta Navigation Aid

This viewer is an interpretive workflow tool. It supports fire safety planning, but it does not replace the official Fire Code, SCDF circulars, or professional judgement.

Read the launch note

Chapter 2

Means of Escape

Chapter 2 governs the design, construction, and maintenance of all exit facilities required to provide safe means of escape from buildings in Singapore. It covers how to determine exit requirements based on occupancy type, occupant load, travel distance, and exit capacity, and sets specific numeric thresholds drawn from Table 2.2A. Special provisions address smoke-free approaches to staircases, exit door requirements, remoteness of exits, and dedicated requirements for persons with disabilities (PWDs).

Scope: Applies to all buildings erected, altered, or changed in occupancy in Singapore, across all purpose groups (PG I–VIII). Specific sub-clauses address residential, commercial, industrial, healthcare, assembly, and basement occupancies.

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • Every storey must be provided with exit facilities sufficient for its occupant load. Vertical exits above ground may serve all above-ground storeys simultaneously; basement exits may only serve basement storeys unless otherwise permitted by SCDF.

    CriticalClause 2.2.1
  • At least two independent exit staircases or other exits are required from every storey, unless otherwise permitted by the Code.

    CriticalClause 2.2.11
  • Minimum clear width of an exit door/exit access opening is 850 mm. No exit, exit staircase, or other exit facility shall be narrower than the minimum specified in Table 2.2A.

    CriticalClause 2.2.7a
  • Where two exits are required from a room or space, each exit must accommodate not less than half the total occupant load.

    CriticalClause 2.2.5b
  • Maximum width of exit staircases is 2 m. Staircases exceeding 2 m must be divided by handrails into sections of 1–2 m width; width beyond 2 m cannot be counted for exit capacity.

    ImportantClause 2.2.8
  • Where a building or floor has mixed occupancies, apply the strictest exit requirements across the entire storey, or determine requirements separately for each section.

    ImportantClause 2.2.2
  • Exit access doors serving rooms with ≤2 persons shall be not less than 610 mm clear width. A single-leaf swing door along means of egress shall not exceed 1.25 m clear width.

    NoteClause 2.2.7b–c

Compliance thresholds

ParameterValueConditionClause
Exit capacity unit of width500 mm (half a metre)All exits, exit staircases, exit passageways, corridors, exit doorsClause 2.2.5a
Fraction of unit width that may be counted≥ 250 mm counts as ½ unit; < 250 mm is disregardedDetermining exit widthClause 2.2.5a
Minimum clear width of exit door / exit access opening850 mmAll exits and exit access openings (general rule)Clause 2.2.7a
Minimum clear width — exit access door (room ≤2 persons)610 mmRoom or space with occupant load of not more than 2 personsClause 2.2.7b
Maximum clear width — single-leaf swing door on egress path1.25 mSingle-leaf swing door along means of egressClause 2.2.7c
Maximum width of exit staircase2 m (only 2 m counts for exit capacity)All exit staircases; width > 2 m requires handrail subdivision into sections of 1–2 mClause 2.2.8
Handrail projection into staircase clear width≤ 80 mm each sideIf projection exceeds 80 mm, clear width is measured from inner sides of handrailsClause 2.2.9a (Note)
One-door occupant load limit — High hazard occupancy25 personsRoom requiring two exits when occupant load exceeds this figureClause 2.2.10 / Table 2.2.10
One-door occupant load limit — Patient accommodation, classrooms, godowns/stores/factories (non-high hazard), assembly50 personsRoom requiring two exits when occupant load exceeds this figureClause 2.2.10 / Table 2.2.10
Smoke-free lobby minimum floor area3 m²Standard smoke-free lobby; if also serves as fire lift lobby: 6 m²Clause 2.2.13b(4)
Smoke-free lobby minimum clear width1.2 mStandard smoke-free lobby; if also serves as fire lift lobby: 2 mClause 2.2.13b(4)
Smoke-free lobby ventilation opening (natural) — minimum area≥ 15% of lobby floor area; each opening ≥ 1 m²Permanent fixed ventilation openings in external wall of smoke-free lobbyClause 2.2.13b(7)(a)
Air well for smoke-free lobby/external corridor ventilation — minimum clear area and width93 m² minimum clear area; 6 m minimum widthAir well used for ventilation of smoke-free lobby, external corridor, external exit passageway, or cross-ventilated lobbyClause 2.2.13b(7)(a); Clause 2.3.11b
Maximum distance from lobby floor area to ventilation air well or external space9 mSmoke-free lobby with natural ventilation openingsClause 2.2.13b(7)(a)
Cross-ventilated corridor/lobby — max distance from ventilation openings12 mNo part of floor area shall exceed 12 m from ventilation openingsClause 2.2.13b(7)(c)(ii)
Number of storeys triggering smoke-free lobby requirementMore than 4 storeys above ground levelEntry at every storey to exit staircase shall be through smoke-free approachClause 2.2.13
Area of refuge — occupant load reductionOne area of refuge → occupant load for vertical exits reduced to 1/2; Two or more areas of refuge → reduced to 1/3Floor area with access to compliant area(s) of refugeClause 2.2.15
Area of refuge — floor area per person0.3 m² per personSizing of area of refuge to hold received occupant load (except healthcare occupancies)Clause 2.2.15a

Interactive decision tree

Start

Determine exit requirements for the storey/building.