Chapter 10

Requirements for Special Installations

Chapter 10 governs the fire safety requirements for four categories of special installations: LPG cylinder systems, solar photovoltaic (PV) systems, energy storage systems (ESS), and electric vehicle (EV) charging stations. It prescribes separation distances, maximum quantities, ventilation standards, and emergency disconnection requirements. Designers and Qualified Persons must ensure each installation type meets the specific siting, protection, and safety provisions before obtaining regulatory approval.

Scope: Applies to commercial, industrial and residential premises installing LPG cylinders for cooking or industrial hot works; buildings with roof-mounted, wall-mounted or wall-integrated PV systems; any premises installing battery-based energy storage systems above threshold stored energy; and buildings with EV charging stations (except PG I buildings for EV requirements).

Source: SCDF Code of Practice for Fire Precautions in Buildings 2023. This is a guidance summary — always verify against the full Fire Code clause text.

Critical points

  • LPG cylinders must be at least 3 m from any fire exit route of a building with only one exit; alternatively a 2-hr fire-rated masonry wall of at least 1.8 m high shall be provided.

    CriticalClause 10.1.3a(2)
  • LPG cylinders shall be at least 1.5 m horizontally from any openings (windows, doors, air vents) of buildings with more than one exit; if not achievable, a 2-hr fire-rated masonry wall of at least 1.8 m high shall be provided.

    CriticalClause 10.1.3a(3)
  • Remote emergency shut-off valve shall be at least 3 m from the edge of the installation, clearly marked and at a suitable height.

    CriticalClause 10.1.3c(2)
  • No ignition source within 3 m from the LPG cylinder installation.

    CriticalClause 10.1.3c(3)
  • Maximum two steel cabinets per manifold for eating outlets; each cabinet may house a maximum of 6 x 50 kg cylinders (total ≤ 600 kg). For industrial applications, up to 10 x 50 kg per cabinet (total ≤ 1000 kg).

    CriticalClause 10.1.3d
  • For kitchen with fixed fire suppression system, activation shall automatically shut off LPG supply.

    ImportantClause 10.1.3c(1)
  • No corrosive, toxic or oxidising materials within 6 m of the cylinder installation.

    ImportantClause 10.1.3b(2)

Compliance thresholds

ParameterValueConditionClause
Min. distance from fire exit route (single-exit building)3 mOr 2-hr fire-rated masonry wall ≥1.8 m high as alternativeClause 10.1.3a(2)
Min. horizontal distance from building openings (multi-exit building)1.5 mOr 2-hr fire-rated masonry wall ≥1.8 m high as alternativeClause 10.1.3a(3)
Min. distance from vehicle parking lot edge3 mAll outdoor LPG installationsClause 10.1.3a(4)
Min. horizontal distance from mechanical air intake (below manifold level)5 mMechanical intake below any part of manifold systemClause 10.1.3a(5)
Min. horizontal distance from mechanical air intake (above manifold level)1.5 mMechanical intake above any part of manifold systemClause 10.1.3a(5)
Min. clearance from top of cylinder/manifold to bottom of window/opening above150 mmCylinders installed below windows or openingsClause 10.1.3a(6)
Min. distance from uncovered opening below cylinder level (≤600 kg)1.5 mDrains, pits, basement openings; total LPG ≤600 kgClause 10.1.3a(7)
Min. distance from uncovered opening below cylinder level (>600 kg)3 mTotal LPG capacity above 600 kgClause 10.1.3a(7)
Min. distance from boundary and fire engine accessway3 mAll outdoor LPG installationsClause 10.1.3a(8)
Min. distance from fire hydrant10 mAll outdoor LPG installationsClause 10.1.3a(9)
Min. separation between two manifold systems (no fire-rated wall)3 mUp to 600 kg installationsClause 10.1.3c(6)
Min. separation between two manifold systems (with 2-hr fire-rated wall)1.5 mUp to 600 kg installations with 2-hr rated wallClause 10.1.3c(6)
Min. height of protective fencing in publicly accessible areas1.8 mLPG cylinders in areas accessible to publicClause 10.1.3b(1)
Max. LPG quantity per manifold — eating outlets600 kgSingle manifold; max 2 cabinets, each with max 6 x 50 kg cylindersClause 10.1.3d(1)
Max. LPG quantity per manifold — industrial applications1000 kgSingle manifold; max 2 cabinets, each with max 10 x 50 kg cylindersClause 10.1.3d(2)
Min. separation between two cabinet clusters (eating outlets)600 mmOutdoor eating outlet installationClause 10.1.3d(1)(b)

Interactive decision tree

DecisionClause 10.1.3d

What is the application type for the outdoor LPG installation?